WUXI SHOUZHUO 180KW CUMMINS DIESEL GENERATOR
|
Generator Set Technical Specification:
|
MODLE:SZ-180C
|
Steady-state voltage regulation rate (%): ≤ ± 1
|
Power: 180KW
|
Voltage fluctuation rate (%): ≤ ± 0.5
|
Rated power factor: COSΦ = 0.8 (lagging)
|
Transient voltage regulation rate (%): +20 to -15
|
Rated output voltage: 400V / 230V
|
Voltage stabilization time (s): ≤1
|
Current Rating: 324A
|
Steady-state frequency regulation rate (%): ≤ ± 1
|
Rated frequency: 50Hz
|
Frequency fluctuation rate (%): ≤ ± 0.5
|
Rated speed: 1500rpm
|
Transient frequency adjust rate (%): + 10 ~ -7
|
Start Control: Electric
|
Frequency stabilization time (S): ≤3
|
Dimensions: 3000×1180×1650 (mm)
|
Unit Weight: 2400kg
|
Diesel Engine Technical Specification:
|
Brand / Origin: Dongfeng Cummins
|
Starting method: DC24V electric start
|
Engine Model: 6CTAA8.3-G2
|
Oil supply: Direct injection
|
Engine power (KW): 180
|
Speed mode: Electric governor
|
Bore * Stroke: 114×135mm
|
Aspiration: Turbocharged
|
Number of cylinders / dare mention Structure: 6 / L-type
|
Cooling: Closed water cooling
|
Fuel consumption (100% load): 230g / kW · h
|
Rotational speed: 1500rpm
|
Overload: 110%
|
( Fuel grade standards): 0 # light diesel oil (at room temperature)
|
Motor Technical Specification:
|
Brand: permanent \ Longgang \ Stanford
|
Output factor: COSΦ = 0.8 (lagging)
|
Model: HJ1-188 (permanent)
|
Rotational speed: 1500rpm
|
Rated power: 180KW
|
Adjustment method: AVR (automatic voltage regulator)
|
Rated voltage: 400V / 230V
|
Connection mode: three-phase four-wire, Y type connection
|
Rated Current (A): 324
|
Protection class: IP22
|
Output frequency: 50Hz
|
Insulation class: H
|
Generator set of standard configuration is as follows:
|
Ø Direct injection internal combustion engine (diesel)
|
Ø AC synchronous generator (single bearing)
|
Ø For the environment 40 ℃ -50 ℃ radiator tank, belt-driven cooling fan, fan safety shield
|
Ø Power generation output air switch, standard control panel
|
Ø Steel common base unit (including: unit damping rubber pad)
|
Ø Dry type air filter, fuel filter, lubricating oil filter, starter motor, and with a self-charging generator
|
Ø Starter batteries and accumulators start connecting cables
|
Ø Industrial 9dB muffler and connecting with standard parts
|
Ø Random data: Diesel engine and generator factory technical documents, brochures and other generators.
|